Conduit fill calculator

Free conduit fill calculator for estimators. Add conductor areas, compare them with the allowed fill for 1, 2 or more conductors, and see how the check works.

Gloved hands pulling red, black, blue and white conductors out of an EMT conduit

Conduit fill calculator

Live NEC Chapter 9 fill check, drawn to scale

Conduit

Leave at 0 to use the standard area for the type and size.

Conductors

Set 1
Set 2
PassLimit 40% for more than 2 conductors
40%0100
19.0%
of conduit filled
1-1/4" EMT, to scale
Conductor area
0.2838 in²
Conduit area
1.496 in²
Allowed area
0.5984 in²
Smallest EMT that passes1"

Not yet reviewed by a licensed electrician. Verify against the current NEC and your AHJ.

This calculator has not yet been reviewed by a licensed electrician. Verify against the current NEC and your AHJ.

Use this calculator to check whether a group of conductors fits in a conduit. It is meant for estimators who need a fast check while sizing raceway. It does not replace the code or the installing electrician's judgment.

How to use it

  1. Choose the conduit type and trade size.
  2. For each conductor size, enter how many conductors you are pulling. The calculator looks up the area of each conductor, including insulation, for the insulation type you choose.
  3. Read the result: total conductor area, the allowed fill for that count of conductors, the percent fill, and whether the check passes.
  4. If the check fails, try the next larger trade size, split the conductors into two raceways, or change the conductor type.

What conduit fill means

Conduit fill is the share of a conduit's inside cross-section that conductors take up. The limit exists so that wires can be pulled without damage and so that heat can leave the bundle. Conductors in a crowded conduit run warmer, which is why a high conductor count also lowers allowable current.

The NEC sets the maximum fill by number of conductors. It is in Chapter 9, in the notes and tables for conduit and tubing, and the limits are in words:

  • One conductor: a little over half of the conduit's inside area may be filled.
  • Two conductors: a little under a third.
  • More than two conductors: about four tenths.

The reason for the two-conductor limit is jamming: two wires of nearly the same size can wedge against the wall of the conduit during a pull. The percentages are in Chapter 9, Table 1. The calculator uses conductor areas (including insulation) from NFPA 70 (NEC) Chapter 9, Table 5, and conduit internal areas from Table 4, built in for THHN/THWN-2 and XHHW/XHHW-2 conductors and common conduit types. The dimensional values come from the 2011 edition of those tables. A secondary source reports that the 2023 edition did not change them for standard conduit and for THHN, THWN-2 and XHHW-2 conductors (see Sources), but we could not check that against the NFPA text. The site does not publish the tables themselves. Check your project against your own copy of the NEC edition your jurisdiction has adopted.

The calculation in plain steps

  1. Add up the area of every conductor, including insulation.
  2. Look up the conduit's internal area for the type and trade size.
  3. Divide the total conductor area by the conduit area. That is the percent fill.
  4. Compare it with the limit for your conductor count. A percent fill at or under the limit passes.

You can also work backward: divide the total conductor area by the limit to find the smallest internal area that works, then choose the smallest trade size at or above it.

Worked examples

The numbers below are made up to show the steps. They are not code values. Use the areas from your own tables.

Example A, more than two conductors. Six conductors with a total area of 0.30 square inches go in a conduit with an internal area of 1.00 square inch. Percent fill is 30%. The limit for more than two conductors is about 40%, so it passes. The smallest conduit area that would work is 0.30 divided by 0.40, or 0.75 square inch.

Example B, two conductors. Two conductors with a total area of 0.40 square inches go in the same 1.00 square inch conduit. Percent fill is 40%. The limit for two conductors is about 31%, so it fails even though the same 40% passed for a larger group. A bigger conduit is needed: 0.40 divided by 0.31 is about 1.29 square inches.

Limits of this calculator

  • It checks fill only. It does not check ampacity, derating for more than three current-carrying conductors, ambient temperature, voltage drop or bending.
  • It does not know your local amendments. The authority having jurisdiction, or AHJ, can require more than the code does.
  • It does not cover short nipples or special cable assemblies, which have their own entries in the code.
  • Fill is not the only reason a pull fails. Long runs, many bends and tight spaces make a pull hard even when the number is within the limit. Long runs also need a voltage drop calculator check.

Enter raceway cost in the electrical estimate template. To find the conduit runs on a drawing set, see electrical blueprint symbols and how to read electrical blueprints. To count every device on the set, see electrical takeoff software.

FAQ

References

Sources

  • NFPA 70, National Electrical Code (NEC), Chapter 9, Table 1 (fill percentages), Table 4 (conduit and tubing dimensions) and Table 5 (conductor dimensions). Values in this calculator follow the 2011 edition. NFPA publishes the code at nfpa.org.
  • "NEC 2023 conduit updates", conduitfillcalculator.pages.dev (a third-party blog, not NFPA): reports no substantive change to Tables 4 and 5 for standard conduit and for THHN, THWN-2 and XHHW-2 in the 2023 edition. https://conduitfillcalculator.pages.dev/blog/nec-2023-conduit-updates
  • Wikipedia, "Electrical conduit": many conductors in one conduit shed heat poorly, so allowable current is reduced.

The calculator has not been reviewed by a licensed electrician. Your adopted NEC edition and local amendments govern.

Free to try on a sample

Upload your drawings

Send a PDF drawing set. The takeoff counts every electrical device by sheet, lists the open questions it found in the drawings, and emails you when it is ready. Export the result as CSV or JSON.

Early access: 1 free project up to 5 plan sheets. Paid plans start at $19.90 a month; cancel anytime.

  • Upload a PDF drawing set
  • Devices counted by sheet
  • Open questions listed for you
  • Export to CSV or JSON