Example takeoff from a public bid set. This is a seven-sheet renovation of one office floor. It has power, data, fire alarm, access control and lighting. It is a larger and messier set than the park restroom. We counted 555 new devices. The drawings come from an open public bid. We leave out the project, owner, city and engineers on purpose.
What this sample shows
- A set with new, existing, relocated and demolished work.
- Tables by group, and the lighting sheet by fixture type.
- A rule that trips up counters: group notation such as
S3 (a,b,c). - Real open questions: a missing panel schedule, an unclear fire alarm symbol, furniture-fed receptacles and an occupancy sensor quantity.
For how to read the columns, see the sample takeoffs hub.
The set
| Sheet | Content |
|---|---|
| E001 | Symbols, notes, sheet list |
| E002 | Existing power riser diagram (not counted) |
| E003 | Panel schedules and details |
| E004 | Luminaire schedule and details |
| E111 | Power and special systems plan (counted) |
| E121 | Lighting plan (counted) |
| ED111 | Demolition plans (summarized only) |
Result by group
These are our own numbers from a run in November 2026 with Claude Sonnet and our takeoff instructions. This is not an independent test: an earlier run on this same set missed grouped switches, and we then added a rule to our instructions (see below). The numbers are new work only.
| Group | New devices |
|---|---|
| Power | 169 |
| Lighting | 139 |
| Switches & controls | 98 |
| Data, fire alarm, access | 148 |
| Panels & equipment | 1 |
| Total new | 555 |
Outside the new total, the run counted 10 relocated exit signs and 6 existing items (a USB receptacle, two linear fixtures and three existing panels).
Full line table
Power: 169 new
| Item | Qty | Status | Confidence |
|---|---|---|---|
| Duplex receptacle 20A, wall (standard, circuits 2B-n, new box) | 97 | new | high |
| Duplex receptacle, "NEW DEVICE, EXISTING OUTLET" (new device in existing box) | 4 | new | medium |
| Duplex receptacle with USB ports (USB), new box | 39 | new | high |
| Duplex USB receptacle, "NEW DEVICE, EXISTING OUTLET" | 1 | new | medium |
| Duplex USB receptacle marked "EXIST." (existing to remain) | 1 | existing | medium |
| GFCI duplex receptacle (GF) | 4 | new | high |
| Special receptacle 6-30R (popcorn popper), circuit 2B-36,38 | 1 | new | high |
| Receptacle in furniture (tag F, 2B-27 and 2B-15) | 4 | new | medium |
| Junction box J for undercarpet wireway 120V connection (keynote 3) | 6 | new | high |
| Junction box J for HVAC controls at new VAV box (2B-23) | 1 | new | medium |
| Junction box J above ceiling for future video displays (with data stub) | 4 | new | medium |
| Junction box J_P furniture power connection (label FP) | 2 | new | medium |
| Surface floor power outlet, 4 x 5-20R, UCW end (power only) | 3 | new | high |
| Surface floor power+data outlet, 4 x 5-20R + 4 keystone, UCW end | 3 | new | high |
Lighting: 139 new
| Item | Qty | Status | Confidence |
|---|---|---|---|
| Type A1 LED 2x2 troffer 3300 lm, 26.3 W - normal circuit | 19 | new | high |
| Type A1 LED 2x2 troffer - emergency circuit 2EHA-5 (shaded) | 6 | new | high |
| Type A2 LED 2x2 troffer 6000 lm, 49 W - normal circuit | 81 | new | high |
| Type A2 LED 2x2 troffer - emergency circuit 2EHA-5 (shaded) | 7 | new | high |
| Type A3 LED 2x2 troffer 7200 lm, 58.6 W | 8 | new | high |
| Type C1 LED 6 in recessed downlight 24.7 W - normal circuit | 13 | new | high |
| Type C1 downlight - emergency circuit 2EHA-5 | 1 | new | high |
| Type UC LED undercabinet strip 2 W/ft (runs, length not measured) | 4 | new | medium |
| Exit sign EXC ceiling-mounted (relocated existing unit per schedule) | 10 | relocated | medium |
| Linear fixtures labelled EXISTING TO REMAIN (no tag) | 2 | existing | medium |
Switches & controls: 98 new
| Item | Qty | Status | Confidence |
|---|---|---|---|
| Dimmer switch S_D (single location, incl. 3 lettered dimmers cS_D bS_D aS_D stack) | 31 | new | high |
| Dimmer switch S_D marked 3-WAY | 4 | new | medium |
| Three-way switch S3 (single) | 4 | new | medium |
| Three-way switch S3 (a,b,c) gang notation - 2 groups x 3 | 6 | new | medium |
| Four-way switch S4 (a,b,c) gang notation - 1 group x 3 | 3 | new | low |
| Wall-box vacancy sensor switch (V) | 6 | new | medium |
| Ceiling occupancy sensor symbol OS (keynote 5: contractor determines quantity) | 37 | new | low |
| Automatic generator transfer device AGTD (keynote 7) | 7 | new | medium |
Data, fire alarm, access: 148 new
| Item | Qty | Status | Confidence |
|---|---|---|---|
| Data/telecom outlet (triangle), wall | 63 | new | medium |
| Telecom outlet with blank cover feeding UCW (keynote 4) | 3 | new | high |
| Data stub (triangle) at J above ceiling for future video | 4 | new | medium |
| Data outlet in furniture (F triangle) | 2 | new | medium |
| J_T furniture telecom pathway box (label FT) | 2 | new | medium |
| AVT 2-gang power/data TV outlet | 4 | new | high |
| Wireless access point AP (owner IT furnishes; EC provides 1-1/4 in conduit) | 13 | new | high |
| Card reader provision CR (box on wall) | 7 | new | high |
| J box 4x4 above ceiling for card reader/lock power (keynote 6, 2B-34) | 7 | new | high |
| Door holder j-box DH (connect to fire alarm) | 2 | new | high |
| FA ceiling horn/strobe 75cd (F in circle, H) | 24 | new | medium |
| FA wall strobe 75cd (square F with circle) | 1 | new | medium |
| FA manual pull station (square F) | 1 | new | medium |
| FA ceiling smoke detector (S hexagon) | 13 | new | high |
| FA ceiling rate-of-rise/heat detector (H hexagon) | 2 | new | high |
Panels & equipment: 1 new
| Item | Qty | Status | Confidence |
|---|---|---|---|
| New 30A 2-pole breaker (N) in panel 2B, ckt 36/38 popcorn popper | 1 | new | high |
| Panel 2B existing (branch circuit panel) | 1 | existing | high |
| Panel 2A existing | 1 | existing | high |
| Panel 2HA existing (lighting 480/277) | 1 | existing | high |
Lighting sheet by fixture type
On sheet E121, tags matched the luminaire schedule. Some fixtures sit on the emergency circuit and are shaded on the plan, so we split them out and then merged them by type.
| Type | Count | Note |
|---|---|---|
| A1 (2x2 troffer) | 25 | 19 normal, 6 emergency |
| A2 (2x2 troffer) | 88 | 81 normal, 7 emergency |
| A3 (2x2 troffer) | 8 | |
| C1 (6 in downlight) | 14 | 13 normal, 1 emergency |
| UC (undercabinet strip) | 4 | runs, length not measured |
| EXC (exit sign) | 10 | relocated, not new |
New, existing, relocated, demolished
Notes and leaders change the status of a device. Examples: "existing to remain", "new device, existing outlet", salvaged and reinstalled. We keep each status as its own line, so the new total holds only new work.
The demolition sheet was not counted item by item. The run gave a rough size with low confidence: about 150 lighting fixtures, about 15 exit or emergency units, and on the power side roughly 100 to 130 receptacles. This is a scale, not a count, and none of it is in the 555.
A rule that matters: S3 (a,b,c)
On the lighting sheet, switches carry notes such as S3 (a,b,c) and S4 (a,b,c). One symbol means one device per listed letter, so three devices.
In an earlier blind run, a different, larger Claude model (Fable 5, no instructions) counted each grouped symbol as one switch. It reported 6 three-way and 1 four-way switch, and 549 new devices in all. The reference count was 10 and 3. That left it 6 switches short on the sheet (4 three-way and 2 four-way).
We added a rule for group notation to our instructions after that miss. The run above counted 10 three-way and 3 four-way switches. Be careful with that comparison: the rule came from this very set, and our instructions were tuned after an earlier run on it, so the result shows the fix works here, not that the method is right on every set. The run flagged the four-way group as low confidence, and raised a question to confirm three devices per group.
Reference comparison
A commercial takeoff service counted the same set (all statuses together). We read its totals from its free preview.
| Commercial service | Fable 5 blind (earlier run) | Sonnet with instructions | |
|---|---|---|---|
| E111 power and special systems | 319 | 319 | 318 |
| E121 lighting | 248 | 240 | 249 |
On E121, all luminaire types, occupancy sensors, AGTD devices and exit signs matched by type. Dimmers were 35 in our run and 34 at the service. On E111 we could not compare item by item, because the service shows only the total for free.
The Sonnet figure of 249 on E121 is the 139 new lighting devices, 10 relocated exit signs and 2 existing linear fixtures, plus the 98 switches and controls (139 + 10 + 2 + 98). The Fable 5 figure of 240 is 8 below the service. The six missed grouped switches explain six of those 8; we did not trace the other two, and we did not recheck the Fable 5 run sheet by sheet, so read that column as a rough guide.
There is no hand-verified reference for this set. Matching another tool is not proof of accuracy.
Open questions found
- Missing emergency panel schedule. The emergency lighting circuit (24 devices) has no panel schedule in the set.
- Unclear fire alarm symbol. One symbol with a subscript H is used 24 times on ceilings. Is it a horn and strobe, or a speaker and strobe? The legend does not say. Who supplies and programs the devices?
- Furniture-fed receptacles. Four receptacles, two data outlets and four furniture connection boxes are tagged as part of the furniture. The furniture vendor may supply them.
- Occupancy sensor quantity. There are 37 sensor symbols, but a note says the contractor determines the quantity. The real number of sensors can be higher, and demolition notes allow reuse of existing ones.
The run also asked about circuits whose plan count did not match the panel row (loads of 0.9 kVA against 1.3 kVA on one circuit), security doors with no hardware drawn, and several "new device, existing outlet" notes.
Panel cross-check
Most circuits matched the panel schedule within about 0.2 kVA. The run flagged three power circuits and one lighting circuit as mismatched and turned each into a question.
Limits
- This is not an independent test. Our instructions were tuned after an earlier run on this set.
- The count has no hand-verified reference. It was compared to a commercial service and to another model run.
- Many receptacle, data and fire alarm lines are medium confidence for the reasons above.
- Demolition quantities are rough.