Voltage drop calculator

Free voltage drop calculator for single-phase and three-phase circuits. Enter current, length and wire resistance per 1000 ft to see volts and percent drop.

Long run of cable tray with cables down the length of a warehouse ceiling

Voltage drop calculator

See what is left at the load, against the 3% and 5% marks

Circuit

Run

Conductor

Leave at 0 to use the table value for the size.
Over 3%, within 5%
Voltage drop
3.10%
Source
240 V
At the load
232.6 V
Volts dropped
7.44 V
Smallest copper for 3% or less
8 AWG

Resistance only: reactance and power factor are ignored. 3% and 5% are recommendations, not code limits.

Not yet reviewed by a licensed electrician. Verify against the current NEC and your AHJ.

This calculator has not yet been reviewed by a licensed electrician. Verify against the current NEC and your AHJ.

Use this calculator to estimate the voltage lost along a conductor run. It is for estimators sizing feeders and long branch circuits while pricing a job. It is a screening tool: use it to see which runs need a closer look, and have the engineer or electrician confirm the final wire size.

How to use it

  1. Pick single-phase or three-phase.
  2. Enter the system voltage, for example 120, 208 or 240.
  3. Enter the load current in amps.
  4. Enter the one-way length of the run in feet.
  5. Enter the conductor resistance per 1000 feet, in ohms. Take it from your own conductor table or the wire manufacturer's data. It depends on size, material (copper or aluminum) and temperature.
  6. Read the result: volts dropped, percent of the system voltage, and the voltage at the load end.

What voltage drop is

Voltage drop is the loss of electrical potential as current flows through a conductor. It comes from the resistance of the wire, and in alternating-current systems also from reactance. It equals current times resistance (or impedance), and the wire's resistance rises with length and falls with a larger cross-section. It also depends on the metal and on temperature. (General background is in the Wikipedia article on voltage drop, listed below.)

Too much drop means lights run dim, motors run hot and draw more current, and some equipment fails to start.

The formula in words

Single-phase. Multiply the current by the one-way length in feet, then by the resistance per 1000 feet, divide by 1000, and multiply by two. The two accounts for the current going out and coming back.

Three-phase. Multiply the current by the one-way length, then by the resistance per 1000 feet, divide by 1000, and multiply by the square root of three, about 1.732. There is no extra factor of two because the phases carry each other's current.

Percent drop. Divide the volts dropped by the system voltage and multiply by 100.

This version uses resistance only. It ignores reactance, which matters for large conductors in steel conduit and for long runs at high current. It also ignores power factor and conductor temperature changes.

The 3% and 5% rule of thumb

NFPA 70 (NEC) informational notes recommend keeping drop within about 3% on a branch circuit and about 5% on the combined feeder and branch circuit, measured to the farthest outlet. They are 210.19(A) Informational Note No. 4 (branch circuits) and 215.2(A)(1) Informational Note No. 2 (feeders). Those note numbers are as cited by trade sources for recent editions (2017 and 2020); we did not check them against the 2023 text, where numbering can shift, so confirm in your adopted edition. These are recommendations in informational notes, not requirements, in most cases. Project specifications, an engineer, or your local authority can set tighter limits. Treat 3% and 5% as a starting point and not a pass-or-fail rule.

Worked examples

The resistance values below are illustrative, not code values. Use values from your own tables.

Example A, single-phase. A 120 V circuit carries 20 A over 100 feet one way. Resistance is taken as 1.24 ohms per 1000 feet. Drop is 2 × 100 × 20 × 1.24 ÷ 1000, which is 4.96 volts. As a percent of 120 V, that is about 4.1%, above the 3% guideline. A larger conductor with lower resistance would bring it down. At 0.78 ohms per 1000 feet the drop is 3.12 volts, about 2.6%.

Example B, three-phase. A 208 V three-phase feeder carries 30 A over 150 feet. Resistance is taken as 0.49 ohms per 1000 feet. Drop is 1.732 × 150 × 30 × 0.49 ÷ 1000, which is about 3.8 volts, or 1.8% of 208 V.

Limits of this calculator

  • It does not choose wire size, check ampacity or apply derating.
  • It ignores reactance and power factor, so results are slightly low for large conductors.
  • It assumes balanced three-phase loads.
  • It uses the resistance you type. A wrong table value gives a wrong answer.
  • Drop is a performance issue, not a safety limit by itself. Safety limits come from ampacity and protection rules.

Add feeder costs to the electrical estimate template. Check conduit size with the conduit fill calculator. Panel loads are in the panel schedule template. To read circuit tags and home runs on a drawing, see electrical blueprint symbols. To count every device on the set, see electrical takeoff software.

FAQ

References

Sources

The calculator has not been reviewed by a licensed electrician, and the examples above use illustrative resistance values.

Free to try on a sample

Upload your drawings

Send a PDF drawing set. The takeoff counts every electrical device by sheet, lists the open questions it found in the drawings, and emails you when it is ready. Export the result as CSV or JSON.

Early access: 1 free project up to 5 plan sheets. Paid plans start at $19.90 a month; cancel anytime.

  • Upload a PDF drawing set
  • Devices counted by sheet
  • Open questions listed for you
  • Export to CSV or JSON